SSW07
Fabricante: WEGCódigo de Erro: E63
Alta
Descrição do Problema

Stall

Solução

Power-on. Reset key. Auto-reset. DIx. Check if programmed acceleration ramp time is lower than the actual acceleration time. Check if motor shaft is locked. Check if the transformer that supplies the motor is saturating and taking too much time to recover from the starting current.

Sintomas Adicionais

LED Fault Flashes twice, LED Ready On. Occurs when the current is greater than twice the nominal motor current for a time longer than 1 second (when parameters are set with factory default values). Momentary motor overload or locked/blocked motor shaft.

Registrado em: 29 de dezembro de 2025 às 21:33