SSW07
Fabricante: WEG•Código de Erro: E62
Descrição do Problema
Start timeout during current limit starting
Solução
Power-on. Reset key. Check if programmed time for the acceleration ramp is inferior to what is needed. Check if value of the programmed current limitation is too low. Check if motor is locked or rotor is blocked.
Sintomas Adicionais
LED Stall Flashing. Activates before full voltage, if the current is greater than twice the nominal motor current. Occurs when the starting time is longer than the time set in the acceleration ramp trimpot. Active only with current limit starting.
Registrado em: 29 de dezembro de 2025 às 21:33