SSW07
Fabricante: WEGCódigo de Erro: E19
Crítica
Descrição do Problema

Short circuit in the SSW power

Solução

Power –on. Manual Reset. Reset key. DIx. Check for short circuit in some thyristor or relay of internal by-pass. Check for external short circuit in parallel with the Soft-Starter power. Check for defect in the current analog reading.

Sintomas Adicionais

Fault LED Flashes 7 times, Ready LED is off. Occurs when the current value in one of the phases is above 30% of the Soft-Starter rated current with the motor stopped (without the Run command).