SSW07
Fabricante: WEG•Código de Erro: Start Timeout Fault
Descrição do Problema
Full voltage is not reached at the end of the acceleration ramp (Acceleration Time trimpot setting). Motor failed to start within the maximum allowed time.
Solução
Check all the connections from the Soft-Starter to the supply network, motor connections, supply network voltage levels, fuses and circuit breakers. Adjust the acceleration time or current limit appropriately.
Sintomas Adicionais
Fault LED flashing twice with the Ready LED on. Motor does not reach nominal speed.
Registrado em: 29 de dezembro de 2025 às 21:33