SSW05
Fabricante: WEGCódigo de Erro: E03
Alta
Descrição do Problema

Phase Loss

Solução

Check for phase fault in the three-phase network, short-circuit or thyristor fault. Verify if the motor is connected and if the motor connection is correct. Check for driving problems with the input contactor or blown input fuses. Check if the 'Motor Current' trimpot or P105 is programmed correctly. Check if motor current consumption is lower than required for actuation of the phase loss protection.

Sintomas Adicionais

LED (Phase Loss) is illuminated. Fault displayed as E03 on HMI.

Registrado em: 29 de dezembro de 2025 às 21:28