UPS- ENTERPRISE
Fabricante: WEGCódigo de Erro: Excessive current peaks
Média
Descrição do Problema

Excessive current peaks at the output causing transient voltage drops.

Solução

Investigate the load current profile and eliminate the causes of the overcurrents. It is recommended that the peak of the load current do not exceed its RMS value three times.

Sintomas Adicionais

Load switched to the reserve line; system locks the static switch after three attempts, keeping the load on the reserve line.

Registrado em: 29 de dezembro de 2025 às 21:16