UPS- ENTERPRISE
Fabricante: WEG•Código de Erro: Excessive current peaks
Descrição do Problema
Excessive current peaks at the output causing transient voltage drops.
Solução
Investigate the load current profile and eliminate the causes of the overcurrents. It is recommended that the peak of the load current do not exceed its RMS value three times.
Sintomas Adicionais
Load switched to the reserve line; system locks the static switch after three attempts, keeping the load on the reserve line.