UPS- ENTERPRISE
Fabricante: WEGCódigo de Erro: Starting Procedure Interrupted
Baixa
Descrição do Problema

The activation sequence was manually suspended.

Solução

Execute the command '3.2 SYSTEM STOP' through menu '3. UPS COMMANDS'. Open all switch-disconnectors of the equipment. To restart, use the '3.1 START THE SYSTEM' command or shut down the UPS and repeat the activation procedure.

Sintomas Adicionais

LCD panel displays the message 'STARTING PROCEDURE INTERRUPTED'.

Registrado em: 29 de dezembro de 2025 às 21:16